Appendix A

MODBUS

Communication

GF-114

Status Messages & Equations

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

89 of 200

Table A-2: C-More Status And Fault Messages - (Continued)

CODE

MESSAGE

DESCRIPTION

17

IGN SWTCH OPEN

DURING IGNITION

The Ignition Position Limit switch on the Air/Fuel valve opened

during ignition.

18

AIRFLOW FAULT

DURING IGN

The Blower Proof Switch opened during ignition.

19

AIRFLOW FAULT

DURING RUN

The Blower Proof Switch opened during run.

20

SSOV FAULT

DURING IGN

The SSOV switch closed or failed to open during ignition.

21

SSOV FAULT

DURING RUN

The SSOV switch closed for more than 15 seconds during run.

22

FLAME LOSS

DURING IGN

The Flame signal was not seen during ignition or lost within 5

seconds after ignition.

23

FLAME LOSS

DURING RUN

The Flame signal was lost during run.

24

HIGH EXHAUST

TEMPERATURE

The High Exhaust Temperature Limit Switch is closed.

25

LOSS OF POWER A power loss occurred. The time and date when power was

restored is displayed.

26

LOSS OF SENSOR Not Currently Used

27

LOSS OF SIGNAL Not Currently Used

28

HIGH O2 LEVEL

Not Currently Used

29

LOW O2 LEVEL

Not Currently Used

30

HIGH CO LEVEL

Not Currently Used

31

SSOV RELAY

FAILURE

A failure has been detected in one of the relays that control the

SSOV.

32

RESIDUAL

FLAME

The Flame signal was seen for more than 60 seconds during

standby.

33

HEAT DEMAND

FAILURE

The Heat Demand Relays on the Ignition board failed to activate

when commanded.

34

IGN SWTCH

CLOSED

DURING PURGE

The Ignition Position Limit switch on the Air/Fuel valve closed

during purge.