Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 14

background image

GF-114

MODBUS

Communication

Chapter 2

OMM-0035_0C

USER MANUAL

Standard Register Assignments

Page

14 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

2.2 C-MORE BOILER CONTROLLER STANDARD REGISTER

ASSIGNMENTS

2.2.1 C-More Boiler Controller Standard Input Register Assignments

The Read Only Input Register addresses are listed in Table 2-1 which follows:

Table 2-1: C-More Boiler Controller Standard Input Register Address Mapping

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

0 (0x0000)

Default Message

Display Code

Enum (1 to 64)

See Appendix A,

Table A-1 for listing

1 (0x0001)

Unit Status

Enum (0, 1, 2, 3, 4, 5)

0 = Unit Status Disabled

1 = Unit Status Standby

2 = Unit Status Manual

3 = Unit Status Remote

4 = Unit Status Auto

5 = Unit Status Fault

2 (0x0002)

Outlet Temp

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

3 (0x0003)

Inlet Temp

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

4 (0x0004)

Aux Temp

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

5 (0x0005)

Outdoor Temp

DEGREES_2 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

6(0x0006)

Exhaust Temp

DEGREES_2 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

7 (0x0007)

FFWD Temp

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

8 (0x0008)

Fire Rate Out

% (0 to 100)

9 (0x0009)

O2 Level

% (0 to 25)

10 (0x000A)

CO Level

PPM (0 to 500)

11 (0x000B)

Run Cycles Low (LSB) int (0 to 65535)

The actual range for run

cycles is from

0 to 999,999

12 (0x000C)

Run Cycles High (MSB) Int (0 to 15)