beautypg.com

1 communication medium, 1 ems master to bms/bms ii/acs slave, 3 ems master to c-more boiler controller slaves – AERCO Modbus Communications Manual User Manual

Page 9: 2 address support, 3 modbus transmission modes, 4 timing specifications, Modbus, Communication, Gf-114

background image

Chapter 1

MODBUS

Communication

GF-114

Introduction & Description

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

9 of 200

1.3.1 Communication Medium

The communication medium for each of the possible Modbus network configurations may vary

depending on the Master/Slave scenario being implemented. Detailed installation procedures

and wiring diagrams for the configurations described in the following paragraphs are provided in

Section 4 of this manual.

1.3.1.1 EMS Master To BMS/BMS II/ACS Slave
The Modbus network connections between the EMS and BMS/BMS II/ACS will depend on the

type of port provide on the EMS Master. If the EMS contains a RS232 port, a direct connection

can be made directly to the BMS/BMS II/ACS RS232 port. For optimum results the wire length

between the EMS and BMS/BMS II/ACS RS232 connection should not exceed 50 feet. If the

EMS Master contains a RS485 port, a RS485-to-RS232 converter will be required to implement

the Modbus network.

1.3.1.2 BMS/BMS II/ACS Master To C-More Boiler Controller Slaves
Up to a total of 32 C-More Boiler Controllers can be connected to a BMS/BMS II/ACS Master on

the Modbus Network. Multi-point drop network connections are made using shielded, twisted-

pair wire. In addition to the Modbus Network Boilers, up to 8 additional Legacy Boilers can be

connected to the BMS Pulse Width Modulation (PWM) wiring connection. The BMS II and ACS

do not support PWM. It should be noted that the BMS, BMS II, and ACS include a Modbus

Pass-Thru feature which, when enabled, permits an EMS to monitor and configure (but not

directly control) the boilers.

1.3.1.3 EMS Master To C-More Boiler Controller Slaves
The number of C-More Boiler Controllers which can be connected to a Modbus Network which

utilizes a third party EMS Master will depend on the EMS’s limitations. Theoretically, the

maximum number of Slave devices is limited to 127. If the EMS contains a RS232 port, a

RS232-to-RS485 converter will be required to provide the necessary RS485 interfaces and

signal levels for the C-More Boiler Controllers. Multi-drop network connections are made using

shielded, twisted-pair wire.

1.3.2 Address Support

Address support is assigned as follows:

BMS/BMS II/ACS Address Support From EMS Master: 128 – 247 (80 – F7 hex)

C-More Address Support From BMS/BMS II/ACS or EMS Master: 1 – 127 (01 – 7F hex)

Broadcast Messages: Address 0 is reserved for all Broadcast messages

1.3.3 Modbus Transmission Modes

Many Modbus Controllers can be set up to transmit using either the ASCII (American Standard

Code for Information Interchange) transmission mode, or the RTU (Remote Terminal Unit)

transmission mode. However, since RTU messages can be formatted using far fewer binary

bits than the corresponding ASCII message, it is far more efficient. Therefore, all Modbus

messages for the AERCO BMS/BMS II/ACS and C-More Boiler Controllers use RTU

transmission ONLY. If a third-party EMS Master is being used in the Modbus network, ensure

that it is set for RTU transmission.

1.3.4 Timing Specifications

As Table 1-1 shows, Baud Rate and Heartbeat Timeout will vary depending on the

Configurations of the AERCO BMS/BMS II/ACS and C-More Boiler Controllers being used in the

Modbus Network. Ensure that the Baud Rate used by the controlling Master (BMS/BMS II/ACS