Status Messages & Equations

Page

90 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

Table A-2: C-More Status And Fault Messages - (Continued)

CODE

MESSAGE

DESCRIPTION

35

PRG SWTCH

CLOSED

DURING IGNITION

The Purge Position Limit switch on the Air/Fuel valve closed

during ignition.

36

SSOV SWITCH

OPEN

The SSOV switch opened during standby.

37

IGNITION BOARD

COMM FAULT

Communication fault between the Ignition board and the CPU

board.

38

WAIT

Prompts the operator to wait.

39

DIRECT DRIVE

SIGNAL FAULT

The direct drive signal is not present or is out of range.

40

REMOTE SETPT

SIGNAL FAULT

The remote setpoint signal is not present or is out of range.

41

OUTDOOR TEMP

SENSOR FAULT

The temperature measured by the Outdoor Air Sensor is out of

range.

42

OUTLET TEMP

SENSOR FAULT

The temperature measured by the Outlet Sensor is out of range.

43

FFWD TEMP

SENSOR FAULT

The temperature measured by the FFWD Sensor is out of range.

44

HIGH WATER

TEMPERATURE

The temperature measured by the Outlet Sensor exceeded the

Temp Hi Limit setting.

45

LINE VOLTAGE

OUT OF PHASE

The High AC voltage is out of phase from the low AC voltage.

46

STEPPER MOTOR

FAILURE

The stepper motor failed to move the valve to the desired position.

47

SETPT LIMITING

ACTIVE

Setpoint temperature has exceeded the maximum allowable

setting.

48

MODBUS COMM

FAULT

The RS485 (Modbus) network information is not present or is

corrupted.