2.3.2 BMS/BMS II Controller Standard Holding Register Assignments

The Holding Register address assignments for the BMS/BMS II/ACS are listed in Table 2-4

which follows. Unless otherwise specified, all Holding Register Menu items are Read/Write

(R/W).

Table 2-4: BMS/BMS II Standard Holding Register Address Mapping

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

0 (0x0000)

(Reserved)

1 (0x0001)

(Reserved)

2 (0x0002)

(Reserved)

3 (0x0003)

(Reserved)

4 (0x0004)

Net Header Set

Temp

40 to 220°F

Valid when Header Set Mode =

Remote Setpt and Remote

Signal = Network

5 (0x0005)

System Start Temp 32 to 120°F

Default = 70°F

6 (0x0006)

System Start Option 0 or 1, 0 = Temp Only,

1 = Temp and Load

Default = 0

7 (0x0007)

Manual Hdr Set

Temp/Internal Setpt 40 to 220°F

Default = 160°F

8 (0x0008)

Bldg Ref Temp

40 to 220°F

Default = 70°F

9 (0x0009)

Indoor Prop Band

0.0 to 20.0°F/°F

(0.5°F/°F increments)

Default = 00.0°F/°F

(Value x 10) (BMS Only)

10 (0x000A)

Indoor Setpoint

Temp

50 to 150°F

Default = 70°F

(BMS Only)

11 (0x000B)

Reset Ratio

0.3 to 3.0

(0.1 increments),

Default = 1.2

(Value x 10)

12 (0x000C)

Max Header Temp

40 to 220°F

Default = 220°F

13 (0x000D)

Min Header Temp

40 to 220°F

Default = 40°F

14 (0x000E)

Start Percent

25 to 100%

Default = 45% (BMS)

Default = 20% (BMS II)

15 (0x000F)

Stop Percent

10 to 45%

Default = 18% (BMS)

Default = 16% (BMS II)

16 (0x0010)

Integral Gain

0.00 to 9.99 Rep/Min

(in 0.01 increments

Default = 0.15 Rep/Min

(Value x 100)

17 (0x0011)

Header Set Mode

0, 1, or 2

0 = Constant Setpt

1 = In/Outdoor Reset

2 = Remote Setpt

Default = 0

(Constant Setpt))