Page 32

background image

GF-114

MODBUS

Communication

Chapter 2

OMM-0035_0C

USER MANUAL

Standard Register Assignments

Page

32 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

Table 2-4: BMS/BMS II Standard Holding Register Address Mapping (Cont.)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

76 (0x004C)

Offset Off Time

Day 7 – Minutes

0 to 59 Minutes

Default = 0

77 (0x004D)

Offset Off Time

Day 1 – Hours

0 to 23 Hours

Default = 0

78 (0x004E)

Offset Off Time

Day 2 – Hours

0 to 23 Hours

Default = 0

79 (0x004F)

Offset Off Time

Day 3 – Hours

0 to 23 Hours

Default = 0

80 (0x0050)

Offset Off Time

Day 4 – Hours

0 to 23 Hours

Default = 0

81 (0x0051)

Offset Off Time

Day 5 – Hours

0 to 23 Hours

Default = 0

82 (0x0052)

Offset Off Time

Day 6 – Hours

0 to 23 Hours

Default = 0

83 (0x0053)

Offset Off Time

Day 7 – Hours

0 to 23 Hours

Default = 0

84 (0x0054)

(Reserved)

85 (0x0055)

Indoor Air Input

0 or 1

0 = 4 – 20 Ma

1 = Thermistor

Default = 1

(Thermistor)

BMS Only

86 (0x0056)

Remote Signal

0 or 1

0 = 4 – 20 Ma

1 = Network

Default = 0

(4 – 20 Ma)

87 (0x0057)

RS232 Mode

0 or 1

0 = Normal

1 = Modbus

Default = 0

(Normal)

88 (0x0058)

RS232 Baud Rate 2400, 4800, 9600, 14.4k,

19.2k

Default = 9600

89 (0x0059)

Number Of

Network Boilers

0 to 32

Default = 0 (for BMS)

Default = 2 (for BMS II)

90 (0x005A)

Min Slave Address 0 to 127

Default = 0

91 (0x005B)

Max Slave

Address

0 to 127,

Default = 0

92 (0x005C)

Net Boiler 1

Address

Address for Network Boiler

1

Default = 0 (for BMS)

Default = 1 (for BMS II)

93 (0x005D)

Net Boiler 2

Address

Address for Network Boiler

2

Default = 0 (for BMS)

Default = 2 (for BMS II)