beautypg.com

Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 56

background image

GF-114

MODBUS

Communication

Chapter 3

OMM-0035_0C

USER MANUAL

Standard Application Operations

Page

56 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

Holding Register addresses 0x0056 and 0x0057 respectively. Also, ensure that the RS232

Baud Rate setting (address 0x0058) matches the EMS Baud Rate being used.
In the Remote Setpoint Mode, the holding register parameter “Net Header Set Temp” (Holding

Register address 0x0004) must be transmitted periodically from the EMS Master to the BMS/

BMS II/ACS Slave. A “Heartbeat” Timer with a timeout period defined by the variable “Network

Timeout” (Holding Register address 0x007D), is reset each time the signal is successfully

received. If the timeout period is exceeded, the BMS/BMS II/ACS will default to its “Fail-Safe”

mode and display a Network Comm Fault.

3.3.3 BMS/BMS II/ACS Master Control of C-More Slaves Via Network

The BMS/BMS II/ACS can also communicate with the up to 32 Network C-MORE Boiler Control

Slaves via the BMS RS485 port. Parallel and Sequential control can be selected as before.

See BMS Manual GF-108M, BMS II Manual GF-124, or ACS Manual GF-131 for additional

information.
The “Number Of Network Boilers” must be entered at location 0x0059 in the Standard Holding

Registers.

The C-More Slave communication addresses (“Net Boiler 1 Address” To “Net Boiler

32 Address”) can either be manually entered in a pre-defined order in the BMS, or they can be

detected from the network and operated in the order they are detected. To manually enter

Network Boiler communication addresses, leave the “Min Slave Address” and “Max Slave

Address” set to their default values of 0. To allow the BMS to automatically detect the Network

Boilers, enter the respective “Min Slave Address” and “Max Slave Address” in their proper

location in the Standard Holding Registers (0x005A, 0X005B). The Max Slave Address must be

no more than 31 above the Min Slave Address.
The fire rate information will be transmitted periodically from the BMS/BMS II/ACS to the C-

MORE boiler controls. A “heartbeat” timer will be reset in the slave each time the control

information is successfully received from the BMS. If a timeout occurs, the slave will default to

its “Fail-Safe Mode” and display “Modbus Comm Fault”.

3.3.4 BMS Combination Mode Boiler Control of C-More Slaves (BMS and ACS

Only)

For BMS applications, the Legacy (PWM) Boilers 5 through 8 can be selected as Combination

Boilers. These Boilers are connected to the BLR 5 - BLR 8 PWM terminal connections (J2).

An AERCO Combination Control Panel (CCP) is necessary to configure this type of setup. It

should be noted that the assigned PWM Combination Boilers can be monitored and configured

on the Modbus Network by assigning a Comm Address between 1 and 127. Refer to BMS

Manual GF-108M for additional information on installation and setup.

NOTE

The C-More Demand Delay function can only be used on C-More

Controllers with software version 2.01 or higher.

For ACS applications, the domestic boilers (up to 8 of 32 network boilers) can be selected as

Combination Boilers. These boilers are connected to the RS485 terminal, JP6. Depending on

the application, ACS Relay Panel may be required. See Application Guide TAG-0049 and ACS

Manual GF-131.