4 modbus network wiring diagrams, Modbus, Communication – AERCO Modbus Communications Manual User Manual

Page 70: Gf-114

background image

GF-114

MODBUS

Communication

Chapter 4

OMM-0035_0C

USER MANUAL

Hardware Setup & Installation

Page

70 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

4.4 MODBUS NETWORK WIRING DIAGRAMS

Sample Modbus Network wiring diagrams for the basic circuit configurations are provided in

paragraphs 4.4.1 through 4.4.3. It should be noted that these diagrams are only intended as a

guide and do not include all possible scenarios. If a third-party EMS is being utilized, refer to the

manufacturer’s manual prior to attempting any network wiring connections.

CAUTION

It is imperative that polarity be maintained between all Modbus

Network connections. The Network will not operate if the proper

polarity is not maintained. Also, twisted-pair wiring shield should

only be terminated at the controlling Master Controller for the

Modbus Network.

4.4.1 Wiring Diagrams for Master EMS Controlling BMS Slaves With Legacy

(PWM) Boilers

Figure 4-11 provides a sample wiring diagram for a BMS (Model 168) being controlled by an

EMS Master equipped with a RS485 port.

4.4.2 Wiring Diagram for Master BMS/BMS II/ACS Controlling Networked C-More

Slaves

Wiring connections for the “Network” Boilers are made at the BMS/BMS II/ACS RS485 port as

shown in Figure 4-12. In addition, for a BMS (only) up to 8 “Legacy” Boilers can be wired to the

PWM terminal strip to allow control of up to 40 Boilers by one BMS. The BMS PWM terminal

connections can also be used to connect AERCO Boilers which utilize older types of control

systems, such as Modular Control Boxes, or C-More Controllers equipped with software version

1.61 or lower. Refer to BMS Manual GF-108M for additional setup details for the PWM “Legacy”

Boilers. BMS II and ACS units do not support PWM, therefore disregard the PWM terminal

connections shown in Figure 4-12. BMS II/ACS units can only operate networked boilers with C-

More control systems.

4.4.3 Wiring Diagram For EMS Master Controlling C-More Controller Slaves

Figure 4-13 provides a sample wiring diagram for an EMS equipped with a RS485 port. If the

EMS contains a 4-wire RS485 port, refer to Figure 4-11, Detail “A” for additional wiring details.