Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 79

background image

Chapter 5

MODBUS

Communication

GF-114

C-More/BMS Software Setup

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

79 of 200

BMS RS485 loop. (This address must be the same as the Comm Address setting in the

C-More Boiler Controller).

8. Press the

HDR TEMP key again until NETW BOILER 2 is shown on the top line of the

display. Use the ▲ and ▼ arrow keys to set the address of the second Boiler being

controlled on the BMS RS485 loop. (This address must be the same as the Comm

Address setting in the C-More Boiler Controller).

9. Repeat step 8 for each additional C-More Boiler being controlled on the BMS RS485

loop.

10. This completes programming for the BMS RS485 Network. Press the

FIELD ADJ key to

exit the Field Adjust Mode. The yellow LED on the key should go off.

IMPORTANT

Boilers #1 thru #8 are reserved for the Legacy Boilers connected to

the Pulse Width Modulation (PWM) connections on the BMS.

Therefore, NETW BOILER 1 is the same as Boiler #9. NETW

BOILER 2 is the same as Boiler #10 and so on.

The BMS is now programmed to control the Networked Boilers, as well as any Legacy Boilers

connected to it. The BMS will automatically detect any C-More Boiler that is programmed for

Network Control as follows:

Boiler Mode = Direct Drive

Remote Signal = Network

Comm Address = Matches one of the NETW BOILER addresses stored in the BMS