Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 35

background image

Chapter 2

MODBUS

Communication

GF-114

Standard Register Assignments

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

35 of 200

Table 2-4: BMS/BMS II Standard Holding Register Address Mapping (Cont.)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

134 (0x0086)

Fault Alarm Boilers

0 = No Blr Faults,

1 = All Blr Faults

Default = 0

135 (0x0087)

4 to 20 mA Current

Offset

-1.00 to 1.00 mA

Default = 0

(BMS II Only)

136 (0x0088)

Return Sensor Offset -10.0 to 10.0

Default = 0

(BMS II Only)

137 (0x0089)

Load Start Pct

1 to Blr Start Level

Default =1 (BMS II Only)

138 (0x008A)

Load Stop Pct

0 to Load Start -1

Default =0 (BMS II Only)

139 (0x008B)

thru

65535 (0xFFFF)

(Reserved For Future

Expansion)

Undefined

0x00A1

Boiler control select

0 = None,

1 = C-More

2 = MLX (BCM)

Default = 0