Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual
Page 20
GF-114
MODBUS
Communication
Chapter 2
OMM-0035_0C
USER MANUAL
Standard Register Assignments
Page
20 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12
Table 2-2: C-More Controller Standard Holding Register Address Mapping
(Continued)
Modbus Data
Address
Decimal (Hex)
Menu Item
Units and Range
Comments
67 (0x0043)
Sensor Log Interval
Enum (0 to 8)
0 = Off
1 = 1 Min.
2 = 5 Min.
3 = 15 Min.
4 = 30 Min.
5 = 1 Hr.
6 = 6 Hrs
7 = 12 Hrs.
8 = 24 Hrs.
Default = 4 (30 min)
68 (0x0044)
Fault Log Pointer
int 0 - 9
69 (0x0045)
Sensor Log Pointer
int 0 - 1199
70 (0x0046)
Time Log Pointer
int 0 - 10239
71 (0x0047)
Thru
65535 (0xFFFF)
(Reserved)
Available for future
expansion.