Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 34

background image

GF-114

MODBUS

Communication

Chapter 2

OMM-0035_0C

USER MANUAL

Standard Register Assignments

Page

34 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

Table 2-4: BMS/BMS II Standard Holding Register Address Mapping (Cont.)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

114 (0x0072)

Net Boiler 23 Address

Address for Network Boiler

23

Default = 0

115 (0x0073)

Net Boiler 24 Address

Address for Network Boiler

24

Default = 0

116 (0x0074)

Net Boiler 25 Address

Address for Network Boiler

25

Default = 0

117 (0x0075)

Net Boiler 26 Address

Address for Network Boiler

26

Default = 0

118 (0x0076)

Net Boiler 27 Address

Address for Network Boiler

27

Default = 0

(119 0x0077)

Net Boiler 28 Address

Address for Network Boiler

28

Default = 0

120 (0x0078)

Net Boiler 29 Address

Address for Network Boiler

29

Default = 0

121 (0x0079)

Net Boiler 30 Address

Address for Network Boiler

30

Default = 0

122 (0x007A)

Net Boiler 31 Address

Address for Network Boiler

31

Default = 0

123 (0x007B)

Net Boiler 32 Address

Address for Network Boiler

32

Default = 0

124 (0x007C)

Network Baud

0=2400, 1=4800, 2=9600,

3=14.4k, 4=19.2k

Default = 2 (9600)

125 (0x007D)

Network Timeout

5 to 240 sec

Default = 60 sec.

126 (0x007E)

Password Lo

0 to 255 (73)

Default = 0

127 (0x007F)

Password Hi

0 to 255 (79)

Default = 0

128 (0x0080)

Modbus Control Type

0 = Round-Robin

1 = Broadcast

Default = 0

(Round Robin)

129 (0x0081)

Modbus Pass-Thru

0 = Disabled

1 = Enabled

Default = 0 (Disabled)

130 (0x0082)

Header Dead Band

1 to 15°F

Default – 5°F (BMS II

Only)

131 (0x0083)

Outside Temp Sensor

Offset

-10°F to 10°F

132 (0x0084)

Ramp Up %/MIN

0 to 300

Default = 20 (BMS II

Only)

133 (0x0085)

Ramp Down %/MIN

0 to 300

Default = 200 (BMS II

Only)