Standard Register Assignments

Page

36 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

2.4 ACS CONTROLLER (ONLY) STANDARD REGISTER

ASSIGNMENTS

IMPORTANT!

All Modbus addresses specified in the following tables are written

generically in hexadecimal format. However, many Building

Automation Systems utilize another form of addressing where: 40001

is added to the generic address for a Holding Register address.

And

30001 is added to the generic address for an Input Register address.
Be sure to check the addressing scheme being used by the BAS that

is being interfaced to the ACS.

2.4.1 ACS Controller Standard Input Register Assignments

The Read Only Input Register assignments for the ACS are listed in Table 2-4 which follows:

Table 2-4: ACS Standard Input Register Address Mapping

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

0 (0x0000)

(Reserved)

1 (0x0001)

Header Temperature

40 to 220°F

2 (0x0002)

Outside Air Temperature

-60 to 120°F

3 (0x0003)

Indoor Air/Return Temperature

40 to 220°F

4 (0x0004)

Fire Rate Out

0 to 100% (out to boilers)

5 (0x0005)

Header Set Temperature

40 to 220°F

6 (0x0006)

Network Address

128 to 247

Default = 128

7 (0x0007)

Total Boilers Fired

0 to 32 (for ACS)

8 (0x0008)

Total Boilers On Line

0 to 32

9 (0x0009)

(Reserved)

10 (0x000A)

Fault/Message Code

0 to 65535

Bit:

0 = Outside Air Sensor

1 = Header Sensor Error

2 = Interlock 1 Error

3 = Interlock 2 Error

4 = Indoor Air Sensor Error/

Return Sensor Error

5 = 4-20mA Input Error

11 (0x000B)

thru

15 (0x000F)

(Reserved)

16 (0x0010)

Lead Boiler Number

1 to 32