Standard Register Assignments

Page

30 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

Table 2-4: BMS/BMS II Standard Holding Register Address Mapping (Cont.)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and

Range

Default/

Comments

32 (0x0020)

Real Time Clock Minutes 00 to 59 Minutes

Present Time

33 (0x0021)

Real Time Clock

Hours

00 to 23 Hours

Present Time

34 (0x0022)

Real Time Clock

Day of Week

1 to 7

Present Day

35 (0x0023)

Real Time Clock

Year

00 to 99

Present Year

36 (0x0024)

Real Time Clock

Day of Month

01 to 31

Present Day of Month

37 (0x0025)

Real Time Clock

Month

01 to 12

Present Month

38 (0x0026)

Offset Temp Day 1

-50 to 50°F

Default = 0°F

39 (0x0027)

Offset Temp Day 2

-50 to 50°F

Default = 0°F

40 (0x0028)

Offset Temp Day 3

-50 to 50°F

Default = 0°F

41 (0x0029)

Offset Temp Day 4

-50 to 50°F

Default = 0°F

42 (0x002A)

Offset Temp Day 5

-50 to 50°F

Default = 0°F

43 (0x002B)

Offset Temp Day 6

-50 to 50°F

Default = 0°F

44 (0x002C)

Offset Temp Day 7

-50 to 50°F

Default = 0°F

45 (0x002D)

Offset On Time

Day 1 – Minutes

00 to 59 Minutes

Default = 0

46 (0x002E)

Offset On Time

Day 2 – Minutes

00 to 59 Minutes

Default = 0

47 (0x002F)

Offset On Time

Day 3 – Minutes

00 to 59 Minutes

Default = 0

48 (0x0030)

Offset On Time

Day 4 – Minutes

00 to 59 Minutes

Default = 0

49 (0x0031)

Offset On Time

Day 5 – Minutes

00 to 59 Minutes

Default = 0

50 (0x0032)

Offset On Time

Day 6 – Minutes

00 to 59 Minutes

Default = 0

51 (0x0033)

Offset On Time

Day 7 – Minutes

00 to 59 Minutes

Default = 0