Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual
Page 40

GF-114
MODBUS
Communication
Chapter 2
OMM-0035_0C
USER MANUAL
Standard Register Assignments
Page
40 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12
Table 2-4: ACS Standard Input Register Address Mapping (Cont.)
Modbus Data
Address
Decimal (Hex)
Menu Item
Units and
Range
Default/
Comments
69 (0x0045)
Net Blr 11 Outlet Temp
40°F to 220°F
70 (0x0046)
Net Blr 12 Outlet Temp
40°F to 220°F
71 (0x0047)
Net Blr 13 Outlet Temp
40°F to 220°F
72 (0x0048)
Net Blr 14 Outlet Temp
40°F to 220°F
73 (0x0049)
Net Blr 15 Outlet Temp
40°F to 220°F
74 (0x004A)
Net Blr 16 Outlet Temp
40°F to 220°F
75 (0x004B)
Net Blr 17 Outlet Temp
40°F to 220°F
76 (0x004C)
Net Blr 18 Outlet Temp
40°F to 220°F
77 (0x004D)
Net Blr 19 Outlet Temp
40°F to 220°F
78 (0x004E)
Net Blr 20 Outlet Temp
40°F to 220°F
79 (0x004F)
Net Blr 21 Outlet Temp
40°F to 220°F
80 (0x0050)
Net Blr 22 Outlet Temp
40°F to 220°F
81 (0x0051)
Net Blr 23 Outlet Temp
40°F to 220°F
82 (0x0052)
Net Blr 24 Outlet Temp
40°F to 220°F
83 (0x0053)
Net Blr 25 Outlet Temp
40°F to 220°F
84 (0x0054)
Net Blr 26 Outlet Temp
40°F to 220°F
85 (0x0055)
Net Blr 27 Outlet Temp
40°F to 220°F
86 (0x0056)
Net Blr 28 Outlet Temp
40°F to 220°F
87 (0x0057)
Net Blr 29 Outlet Temp
40°F to 220°F
88 (0x0058)
Net Blr 30 Outlet Temp
40°F to 220°F
89 (0x0059)
Net Blr 31 Outlet Temp
40°F to 220°F
90 (0x005A)
Net Blr 32 Outlet Temp
40°F to 220°F
91 (0x005B)
PLANT DT STATUS
10°F to 100°F
When Return
Sensor Mode =
NORMAL
92 (0x005C)
Net Blr 1 Code
0 to 64 for Cmore;
0 to 65535 for MLX
(BCM)