OMM-0035_0C

USER MANUAL C-More/BMS II/ACS Software Setup

Page

84 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

CHANGE, ▲ and ▼ arrow keys, select the appropriate baud rate being used on the

Modbus Network. Press the

ENTER key to store the selected baud rate.

6. Scroll to the MODBUS ADDRESS option in the RS232 MENU. Using the

CHANGE key,

and the ▲ and ▼ arrow keys, select the desired address for the BMS II/ACS on the

Modbus Network. When the address is selected, press the

ENTER key to store the

address in memory.

7. Next, scroll to the NETWORK TIMEOUT option in the RS232 MENU. Press the

CHANGE

key and then select the maximum allowable time (in seconds) for the EMS (or BAS) to

refresh the Remote Setpoint information being sent to the BMS II/ACS. AERCO

recommends that a time be selected that is at least 3 times the normal refresh rate. This

will allow for the loss of 1 or 2 transmissions without timing out. This completes the

required entries in the RS232 MENU.

8. Press the

MENU key and enter the FIELD ADJUST MENU.

9. Using the ▲ and ▼ arrow keys, scroll through the FIELD ADJUST MENU until the HDR

SET MODE option is displayed.

10. If REMOTE SETPT is not shown in the second line of the display, press the

CHANGE

key and toggle the display to REMOTE SETPT.

11. Press the

ENTER key to store the REMOTE SETPT setting.

12. While still in the FIELD ADJUST MENU, scroll to the REMOTE SIGNAL option.
13. If MODBUS is not shown in the second line of the display, press the

CHANGE key and

toggle the display to MODBUS.

14. Press the

ENTER key to store the setting.

15. This completes all required menu entries for this mode.

The BMS II/ACS is now programmed for Remote Setpoint Operation from an EMS Master. In

the event of a Modbus signal interruption, AERCO recommends that the FAIL SAFE MODE

setting in the (CONFIGURATION MENU) be set to CONSTANT SETPT if you want the BMS II to

continue running the Boilers in the CONSTANT SETPT Mode. In this case, ensure that the

INTERNAL SETPT (Field Adjust Menu) is set to the desired setpoint temperature.

6.4 BMS II/ACS SETUP AS MASTER TO C-MORE BOILER

CONTROLLERS

To set up the BMS II/ACS as a Master to control C-More Boiler Slaves, options must be set in

the RS485 Menu as follows:

1. Using the

MENU key on the BMS II/ACS front panel, select the RS485 MENU.

2. Scroll through the RS485 Menu and select the RS485 BAUDRATE option. The second

line of the display will show the currently selected RS232 Baud Rate (2400, 4800, 9600

or 19200).

3. If 9600 is not displayed, press the

CHANGE key.

4. Using the ▲ and ▼ arrow keys, scroll through the menu option choices until 9600 is

displayed.

5. With a RS485 Baud Rate of 9600 displayed, press the

ENTER key to store the setting in

memory.