Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 15

background image

Chapter 2

MODBUS

Communication

GF-114

Standard Register Assignments

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

15 of 200

Table 2-1: C-More Boiler Controller Standard Input Register Address Mapping

(Continued)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

13 (0x000D)

Run Hours

Low (LSB)

int (0 to 65535)

The actual range for run hours

is from

0 to 999,999

14 (0x000E)

Run Hours

High (MSB)

int (0 to 15)

15 (0x000F)

Flame Strength

% (0 to 100)

16 (0x0010)

Active Set point

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions

17 (0x0011)

Fire Rate In

% (0 to 100)

18 (0x0012)

Manual Fire Rate

% (0 to 100)

Only applicable when in the

Manual Mode and controlled by

the front panel interface

19 (0x0013)

Comm Address

Int (0 to 127)

Default = 0

Comm Address 0 disables the

Controller’s Modbus

communications

20 (0x0014)

Software Version

int (0 to 65535)

21 (0x0015)

22 (0x0016)

(Reserved)

23 (0x0017)

Fault Log Code

Fault Log

24 (0x0018)

Fault Log

Cycle (LOW)

int (0 to 65535)

The internal variable type for

fault log display cycle is long

and the range is 0 to 999999

25 (0x0019)

Fault Log

Cycle (HIGH)

Int (0 to 15)

26 (0x001A)

Fault Log

Date

Int (1 to 65535)

1 count/day

27 (0x001B)

Fault Log

Time

Int (0 to 1439)

1 count/min.

28 (0x001C)

Sensor Log

Active Setpoint

DEGREES_1 (0 to 1000)

See Appendix A,

Tables A-2 and A-3 for

Conversions