Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 51

background image

Chapter 2

MODBUS

Communication

GF-114

Standard Register Assignments

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

51 of 200

Table 2-5: ACS Standard Holding Register Address Mapping (Cont.)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

150 (0x0096)

DEADBAND HIGH 0 to 25°

Default = 1

151 (0x0097)

DEADBAND LOW

0 to 25°

Default = 1

152 (0x0098)

SETPOINT DOWN

RATE

0 to 100°/Min

Default = 100

153 (0x0099)

DEMAND OFSET

0 to 100°

Default = 0

154 (0x009A)

PLANT DT LIMIT

10 to 100°

Default = 40

155 (0x009B)

BOILER DELAY

TIME

10 to 999 Sec

Default = 30

156 (0x009C)

VALVE WAIT

STATE

0 = Off

1 = Current State

? Default = 0

157 (0x009D)

BOOST TEMP

Hdr Low Limit to Hdr High Limit

Default = 140

158 (0x009E)

VALVE WAIT TIME 0 to 500 Sec

Default = 120

159 (0x009F)

RETURN TEMP

BOOST DISABLE

Off, -80° to +80°

Default = Off

160 (0x00A0)

MODBUS ON.OFF

0 to 2

0 = Front Panel Off

1 = On

2 = Modbus Off

Default = 0

161 (0x00A1)

BOILER CONTROL

SELECT

0 to 2

0 = None

1 = Cmore

2 = MLX (BCM)

Default = 0

162 (0x00A2)

BOOST MAX

TIMER

0 (Off), 1 to 999 Min

Default = 0

163 (0x00A3)

Thru

65535 (0Xffff)

(Reserved For

Future Expansion)

Undefined