Standard Register Assignments

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

47 of 200

Table 2-5: ACS Standard Holding Register Address Mapping (Cont.)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

76 (0x004C)

Offset Off Time

Sat. – Minutes

0 to 59 Minutes

Default = 0

77 (0x004D)

Offset Off Time

Sun. – Hours

0 to 23 Hours

Default = 0

78 (0x004E)

Offset Off Time

Mon. – Hours

0 to 23 Hours

Default = 0

79 (0x004F)

Offset Off Time

Tue. – Hours

0 to 23 Hours

Default = 0

80 (0x0050)

Offset Off Time

Wed. – Hours

0 to 23 Hours

Default = 0

81 (0x0051)

Offset Off Time

Thu. – Hours

0 to 23 Hours

Default = 0

82 (0x0052)

Offset Off Time

Fri. – Hours

0 to 23 Hours

Default = 0

83 (0x0053)

Offset Off Time

Sat. – Hours

0 to 23 Hours

Default = 0

84 (0x0054)

(Reserved)

85 (0x0055)

Not Applicable

86 (0x0056)

Remote Signal

0 or 1

0 = 4 – 20 Ma

1 = Network

Default = 0

(4 – 20 Ma)

87 (0x0057)

RS232 Mode

0 or 1

0 = Normal

1 = Modbus

Default = 1

(Modbus)

88 (0x0058)

RS232 Baud Rate

0=2400, 1=4800, 2=9600,

3=14400, 4=19200

2 = 9600

89 (0x0059)

Number Of Network

Boilers

0 to 32

Default = 2

90 (0x005A)

Min Slave Address 0 to 127

Default = 0

**91 (0x005B)

Max Slave Address 0 to 127,

Default = 0

**92 (0x005C)

Net Boiler 1

Address

Address for Network Boiler 1 Default = 1

**93 (0x005D) Net Boiler 2

Address

Address for Network Boiler 2 Default = 2