Standard Register Assignments

Page

24 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

Table 2-3: BMS/BMS II Standard Input Register Address Mapping (Continued)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Comments

47 (0x002F)

Boiler 31 Status (Net Boiler 23)

Boiler 23 Status (BMS II)

119 = Not On-Line

120 = On-Line But Not

Fired

1–40 = Fired & Sequence

121 = On-Line But

Disabled

122 = On-Line But

Faulted

48 (0x0030)

Boiler 32 Status (Net Boiler 24)

Boiler 24 Status (BMS II)

Same As Above

49 (0x0031)

Boiler 33 Status (Net Boiler 25)

Boiler 25 Status (BMS II)

Same As Above

50 (0x0032)

Boiler 34 Status (Net Boiler 26)

Boiler 26 Status (BMS II)

Same As Above

51 (0x0033)

Boiler 35 Status (Net Boiler 27)

Boiler 27 Status (BMS II)

Same As Above

52 (0x0034)

Boiler 36 Status (Net Boiler 28)

Boiler 28 Status (BMS II)

Same As Above

53 (0x0035)

Boiler 37 Status (Net Boiler 29)

Boiler 29 Status (BMS II)

54 (0x0036)

Boiler 38 Status (Net Boiler 30)

Boiler 30 Status (BMS II)

Same As Above

55 (0x0037)

Boiler 39 Status (Net Boiler 31)

Boiler 31 Status (BMS II)

Same As Above

56 (0x0038)

Boiler 40 Status (Net Boiler 32)

Boiler 32 Status (BMS II)

Same As Above

57 (0x0039)

I/O Status

0 to 255

Bit map of Input/Output

status (BMS II Only)

Bit 0 = AUX Relay

Bit 1 = Fault Relay

Bit 2 = Sys Start Relay

Bit 3 = Empty

Bit 4 = Setback

Bit 5 = Interlock 2

Bit 6 = Interlock 1

Bit 7 = Empty

58 (0x003A)

Return Sensor Temp

40 °F to 220°F

BMS II Only