Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual
Page 39
Chapter 2
MODBUS
Communication
GF-114
Standard Register Assignments
USER MANUAL
OMM-0035_0C
05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Page
39 of 200
Table 2-4: ACS Standard Input Register Address Mapping (Cont.)
Modbus Data
Address
Decimal (Hex)
Menu Item
Units and Range
Default/
Comments
55 (0x0037)
Boiler 31 Status
(Net Boiler 31)
119 = Not On-Line
120 = On-Line But Not
Fired
1–40 = Fired &
Sequence
121 = On-Line But
Disabled
122 = On-Line But
Faulted
56 (0x0038)
Boiler 32 Status
(Net Boiler 32)
Same As Above
57 (0x0039)
I/O Status
00 to 255
Bit map of Input/Output
Status:
Bit 0 = AUX Relay
Bit 1 = Fault Relay
Bit 2 = Sys Start Relay
Bit 3 = Empty
Bit 4 = Setback
Bt 5 = Interlock 2
Bit 6 = Interlock 1
Bit 7 = Empty
58 (0x003A)
Return Sensor Temp
40°F to 220°F
When Ret Sensor Mode
= Normal
59 (0x003B)
Net Blr 1 Outlet Temp
40°F to 220°F
When Blr Cntl Type = 1
or 2
60 (0x003C)
Net Blr 2 Outlet Temp
40°F to 220°F
61 (0x003D)
Net Blr 3 Outlet Temp
40°F to 220°F
62 (0x003E)
Net Blr 4 Outlet Temp
40°F to 220°F
63 (0x003F)
Net Blr 5 Outlet Temp
40°F to 220°F
64 (0x0040)
Net Blr 6 Outlet Temp
40°F to 220°F
65 (0x0041)
Net Blr 7 Outlet Temp
40°F to 220°F
66 (0x0042)
Net Blr 8 Outlet Temp
40°F to 220°F
67 (0x0043)
Net Blr 9 Outlet Temp
40°F to 220°F
68 (0x0044)
Net Blr 10 Outlet Temp 40°F to 220°F