beautypg.com

Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual

Page 93

background image

Appendix A

MODBUS

Communication

GF-114

Status Messages & Equations

USER MANUAL

OMM-0035_0C

05/18/12 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Page

93 of 200

Table A-5: BCM (Boiler Communication Module) Fault Codes

CODE

DESCRIPTION

EFFECT

CORRECTION

RESET

17

Boiler Pipe is frozen.

FlowSensor temp. is

36°F or less.

Ignition is

inhibited. Pump

runs for 5 min

at max speed.

Carefully defrost

boiler

AUTOMATIC - when

FlowSensor is greater

than 41°F.

18

Maximum Δ-

temperature

protection. Flow

temperature - Return

Temperature > Water

Δ-Temp Protection +

50°F

All burners

turned OFF and

Pump ON at

maximum

speed.

Check the

system

installation.

AUTOMATIC - when Δ-

temperature < Water Δ-

Temp Protection.

19

High outlet

temperature.

FlowSensor

temperature > 203°F.

All burners

turned OFF and

Pump ON at

maximum

speed.

Check Flow

Sensor or

system pump

AUTOMATIC - when

FlowSensor < 176°F.

38

Settings Corrupted

Ignition is

inhibited. Pump

runs for 5 min

at max speed.

Re-program the

settings.

Contact Factory

MANUAL - push reset

switch or cycle power.

50

Internal Failure

Ignition is

inhibited.

Contact Factory

for new BCM.

MANUAL - cycle the

power.

58

FlowSensor fault.

All burners

turned OFF.

Check flow

sensor or wiring. AUTOMATIC

97

Standby. No remote

control detected and

Request input is

open.

Ignition is

inhibited.

Close Request

input for Manual

operation.

MANUAL - push reset

switch or cycle power.

98

No BMM detected.

Ignition is not

possible.

Check the BMM

eBus wiring.

MANUAL - push reset

switch or cycle power.