Modbus, Communication, Gf-114 – AERCO Modbus Communications Manual User Manual
Page 46

GF-114
MODBUS
Communication
Chapter 2
OMM-0035_0C
USER MANUAL
Standard Register Assignments
Page
46 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12
Table 2-5: ACS Standard Holding Register Address Mapping (Cont.)
Modbus Data
Address
Decimal (Hex)
Menu Item
Units and Range
Default/
Comments
52 (0x0034)
Offset On Time Day 1 – Hours 00 to 23 Hours
Default = 0
53 (0x0035)
Offset On Time Day 2 – Hours 00 to 23 Hours
Default = 0
54 (0x0036)
Offset On Time Day 3 – Hours 00 to 23 Hours
Default = 0
55 (0x0037)
Offset On Time Day 4 – Hours 00 to 23 Hours
Default = 0
56 (0x0038)
Offset On Time Day 5 – Hours 00 to 23 Hours
Default = 0
57 (0x0039)
Offset On Time Day 6 – Hours 00 to 23 Hours
Default = 0
58 (0x003A)
Offset On Time Day 7 – Hours 00 to 23 Hours
Default = 0
59 (0x003B)
Offset Enable
0 or 1
0 = Disabled
1 = Enabled
Default = 0
(Disabled)
60 (0x003C)
Header Temp Offset
-10 to 10°F
Default = 0°F
61 (0x003D)
System Start Interlock
1, 2 or 3
1 = Intlk1 Opens Start Relay
2 = Intlk2 Opens Start Relay
3 = Either Intlk Opens Start
Relay
Default = 1
(Intlk 1)
62 (0x003E)
Thru
69 (0x0045)
(Reserved)
70 (0x0046)
Offset Off Time Sun. –
Minutes
0 to 59 Minutes
Default = 0
71 (0x0047)
Offset Off Time Mon. –
Minutes
0 to 59 Minutes
Default = 0
72 (0x0048)
Offset Off Time Tue.– Minutes 0 to 59 Minutes
Default = 0
73 (0x0049)
Offset Off Time Wed.–
Minutes
0 to 59 Minutes
Default = 0
74 (0x004A)
Offset Off Time Thu – Minutes 0 to 59 Minutes
Default = 0
75 (0x004B)
Offset Off Time
Fri. – Minutes
0 to 59 Minutes
Default = 0