Page 46

background image

GF-114

MODBUS

Communication

Chapter 2

OMM-0035_0C

USER MANUAL

Standard Register Assignments

Page

46 of 200 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph.: 800-526-0288 05/18/12

Table 2-5: ACS Standard Holding Register Address Mapping (Cont.)

Modbus Data

Address

Decimal (Hex)

Menu Item

Units and Range

Default/

Comments

52 (0x0034)

Offset On Time Day 1 – Hours 00 to 23 Hours

Default = 0

53 (0x0035)

Offset On Time Day 2 – Hours 00 to 23 Hours

Default = 0

54 (0x0036)

Offset On Time Day 3 – Hours 00 to 23 Hours

Default = 0

55 (0x0037)

Offset On Time Day 4 – Hours 00 to 23 Hours

Default = 0

56 (0x0038)

Offset On Time Day 5 – Hours 00 to 23 Hours

Default = 0

57 (0x0039)

Offset On Time Day 6 – Hours 00 to 23 Hours

Default = 0

58 (0x003A)

Offset On Time Day 7 – Hours 00 to 23 Hours

Default = 0

59 (0x003B)

Offset Enable

0 or 1

0 = Disabled

1 = Enabled

Default = 0

(Disabled)

60 (0x003C)

Header Temp Offset

-10 to 10°F

Default = 0°F

61 (0x003D)

System Start Interlock

1, 2 or 3

1 = Intlk1 Opens Start Relay

2 = Intlk2 Opens Start Relay

3 = Either Intlk Opens Start

Relay

Default = 1

(Intlk 1)

62 (0x003E)

Thru

69 (0x0045)

(Reserved)

70 (0x0046)

Offset Off Time Sun. –

Minutes

0 to 59 Minutes

Default = 0

71 (0x0047)

Offset Off Time Mon. –

Minutes

0 to 59 Minutes

Default = 0

72 (0x0048)

Offset Off Time Tue.– Minutes 0 to 59 Minutes

Default = 0

73 (0x0049)

Offset Off Time Wed.–

Minutes

0 to 59 Minutes

Default = 0

74 (0x004A)

Offset Off Time Thu – Minutes 0 to 59 Minutes

Default = 0

75 (0x004B)

Offset Off Time

Fri. – Minutes

0 to 59 Minutes

Default = 0