Commissioning
Operating Manual PNOZ s30
1001715-EN-13
54
Level Menu designation
Description
Settings
3
Delay
Effect
(Rel.1 ... Out 4)
Default:
On delay
Enter whether the delay time is to
be activated when switching on,
switching off, or switching on and
off.
- On
- Off
- On Off
3
Delay
Time (Rel.1 ... Out 4)
Default:
tdO: 0 ms
Select delay time for the respec-
tive output
0 ... 30.0 s
1
Output Out
Logic
Setting for the switching direction
of the semiconductor outputs
2
Output
(Out 1 ... Out 4)
Logic
Default:
N/O contact
Select the switching direction of
the semiconductor outputs Out 1
... Out 4:
N/O contact (normally energised
mode)
N/C contact (normally de-ener-
gised mode)
- N/O contact
- N/C contact
1
Name of
Configuration
Default:
Default
Enter name of the configuration
The name may be a max. of 8
characters in length
It is stored on the chip card
........
1
Password
Settings
Change passwords
Please note: In the "Default Set-
tings" menu, the passwords are re-
set to the default setting: 0000.
2
Master
PW
Change master password
0000 ... 9999
2
Customer
PW
Change customer password
0000 ... 9999
2
Language
Default:
English
Select menu language
- English
- German
- French
1
Default
Settings
Select whether the parameters are
to be reset to the default settings
YES: All parameters are reset to
the default values. The language
is set to English and all passwords
are set to 0000.
- ESCAPE
- YES