6 commissioning, 1 wiring, 1 general wiring guidelines – Pilz PNOZ s30 24-240VACDC 2 n/o 2 n/c User Manual
Page 30: 2 pin assignment of rj45 socket, 3 supply voltage, Section 6, Commissioning, Wiring, General wiring guidelines, Pin assignment of rj45 socket

Commissioning
Operating Manual PNOZ s30
1001715-EN-13
30
Commissioning
Wiring
General wiring guidelines
Note:
}
Information given in the "Technical details" must be followed.
}
Use copper wire that can withstand 75 °C.
}
The cable used to connect the rotary encoders and the proximity switches must be
shielded (see connection diagrams in the chapter entitled "EMC-compliant wiring").
}
The shield may only be connected to earth at a single point.
}
Earth loops should be avoided.
}
If possible, the connections for the various earth potentials (GND, S21, Y30 und A2)
should not be connected on the PNOZ s30 but should be connected directly to the
GNDs on the connected units, otherwise noise susceptibility may be increased signifi-
cantly (conductor loops are not permitted).
Pin assignment of RJ45 socket
RJ45 socket
8-pin
PIN
Track
8 1
1
S
2
GND
3
Z
4
A
5
/A
6
/Z
7
B
8
/B
Supply voltage
Supply voltage
AC
DC
A1
L1
N
A2
A1
L+
A2
L-
6
6.1
6.1.1
6.1.2