New server engagement policy – Dell POWEREDGE M1000E User Manual
Page 209

•
CMC does not support
automated
power-down of a lower priority server to allow power up of a higher priority
server; however, you can perform user-initiated power-downs.
•
Changes to the PSU redundancy policy are limited by the number of PSUs in the chassis. You can select any of the
three PSU redundancy configuration settings listed in
Default Redundancy Configuration
.
New Server Engagement Policy
If a new server that is turned on exceeds the power available for the chassis, CMC may decrease the power to the low-
priority servers. This allows more power for the new server. This happens if:
•
The administrator had configured a power limit for the chassis that is below the power required for full power
allocation to the servers.
•
Insufficient power is available for the worst-case power requirement of all servers in the chassis.
If enough power cannot be freed by reducing the power allocated to the lower priority servers, the new server may not
be allowed to turn on.
The highest amount of sustained power required to run the chassis and all of the servers, including the new one, at full
power is the worst-case power requirement. If that amount of power is available, then no servers are allocated power
that is less than the worst-case power needed and the new server is also allowed to turn on.
The following table provides the actions taken by CMC when a new server is turned on in the scenario described earlier.
Table 38. CMC Response When a Server Power-On is Attempted
Worst Case Power is Available
CMC Response
Server Power On
Yes
No power conservation is required
Allowed
No
Perform power conservation:
•
Power required for new server is available
•
Power required for new server is not available
Allowed
Disallowed
If a PSU fails, it results in a non-critical health state and a PSU failure event is generated. The removal of a PSU results
in a PSU removal event.
If either event results in a loss of redundancy, based on power allocations, a
loss of redundancy
event is generated.
If the subsequent power capacity or the user power capacity is greater than the server allocations, servers have
degraded performance or, in a worse case, servers may be powered down. Both conditions are in reverse-priority order,
that is, the lower priority servers are powered down first.
The following table provides the firmware response to a PSU power down or removal as it applies to various PSU
redundancy configurations.
Table 39. Chassis Impact from PSU Failure or Removal
PSU Configuration
Dynamic PSU
Engagement
Firmware Response
Grid Redundancy
Disabled
CMC alerts you of loss of Grid Redundancy.
Power Supply
Redundancy
Disabled
CMC alerts you of loss of Power Supply Redundancy.
No Redundancy
Disabled
Decrease power to low priority servers, if needed.
Grid Redundancy
Enabled
CMC alerts you of loss of Grid Redundancy. PSUs in standby
mode (if any) are turned on to compensate for power budget lost
from the PSU failure or removal.
209