Severity
Message
Cause
Critical
The power supplies are not redundant.
Insufficient resources to maintain normal
operations.
One or more PSU have failed or removed and the
system lacks sufficient power to maintain normal
operations. This could cause servers to power down.
Warning
The control panel ambient temperature is
greater than the upper warning threshold.
Chassis/Enclosure intake temperature exceeded the
warning threshold.
Critical
The control panel ambient temperature is
greater than the upper warning threshold.
Chassis/Enclosure intake temperature exceeded the
warning threshold.
Critical
CMC redundancy is lost.
CMC no longer redundant. This happens if the standby
CMC is removed.
Critical
All event logging is disabled.
The Chassis/Enclosure cannot store events to the
logs. This usually indicates a problem with the control
panel or control panel cable.
Warning
Log is full.
Chassis has detected that only one more entry can be
added to the CEL (hardware log) before it is full.
Warning
Log is almost full.
Chassis event log is 75% full.
Table 48. Fan Status Screens
Severity
Message
Cause
Critical
Fan
lower critical threshold.
The speed of the specified fan is not sufficient to
provide enough cooling to the system.
Critical
Fan
upper critical threshold.
The speed of the specified fan is too high, usually due
to a broken fan blade.
Table 49. IOM Status Screens
Severity
Message
Cause
Warning
A fabric mismatch detected on I/O module
The IO module fabric does not match that of the
server or the redundant I/O module.
Warning
A link tuning failure detected on I/O module
The IO module could not be set to correctly use the
NIC on one or more servers.
Critical
A failure is detected on I/O module
The I/O module has a fault. The same error can also
happen if the I/O module is thermal-tripped.
Table 50. iKVM Status Screen
Severity
Message
Cause
Warning
Console is not available for Local KVM.
Minor failure, such as corrupted firmware.
Critical
Local KVM can not detect any hosts.
USB host enumeration failure.
Critical
OSCAR, on screen display is not functional
for the Local KVM.
OSCAR failure.
Non- Recoverable
Local KVM is not functional, and is powered
off.
Serial RIP failure or USB host chip failure.
240