P4 Product Change and Product Select
Timing
12.1 One Pulse Set Overview
The Product Change line signals the Sensor to stop what it is doing and begin counting pulses on the Product
Select line. The number of pulses indicates to the Sensor the inspection address at which to begin executing
the inspection. The only pulses counted are those that occur when the Product Change input is active. As
shown in the diagram below, a Product Select input pulse that occurs when the Product Change input is not
active is NOT counted.
If the Sensor is in Run mode, the Product Change line should be activated only when the Sensor Green Ready
LED is ON. If the Product Change line is activated when the Sensor is in Run mode but performing an inspection
(not Ready), the current inspection will be aborted, and the Sensor will proceed to load the inspection at the
indicated address.
If the Product Change line is activated when the Sensor is not in Run mode (Setup mode, for example), then
the Sensor will go to the address indicated (address number four in this case) and begin executing. The
maximum number of pulses is limited by the number of inspections possible on the Sensor.