Chapter 5

Connecting the Kinetix 5500 Drive System

Figure 36 - Corner Grounded (B-phase) Power Configuration (Delta Secondary)

Refer to

Power Wiring Examples

beginning on

page 190

for input power

interconnect diagrams.

Ungrounded Power Configurations

The ungrounded power configuration (

Figure 37

) does not provide a neutral

ground point.

L3

L1

L2

1

2

L3

L2

L1

1

2

Transformer (Delta) Secondary

Bonded Cabinet

Ground

Transformer

Ground Grid or

Power Distribution Ground

Connect to ground stud.

Three-phase

AC Line Filter

Input Fusing

Kinetix 5500 Servo Drive

(top view)

IMPORTANT

Even though corner-grounded power configurations have a ground
connection, treat them as ungrounded when installing Kinetix 5500 drive
systems.

IMPORTANT

If you determine that you have ungrounded or high-impedance grounded
power distribution in your facility, you need to remove the grounding screws.

Refer to

Removing the Grounding Screws in Ungrounded Power Configurations

on

page 71