Shared ac/dc hybrid configurations – Rockwell Automation 2198-Hxxx Kinetix 5500 Servo Drives User Manual User Manual
Page 217
Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
217
Sizing Multi-axis Shared-bus Configurations
Appendix C
Shared AC/DC Hybrid Configurations
In shared AC/DC hybrid configurations, three-phase AC input power is
supplied to two or more (leader) drives that act as converters. This parallel
converter configuration increases the DC power supplied to the inverter
(follower) drives:
• The leftmost drives in a hybrid configuration act as parallel converter
drives and must be of the same power rating (catalog number).
• Shared DC (inverter) drives mounted to the right of the shared AC/DC
(converter) drives must have the same or lower power rating (catalog
number) than the shared AC/DC drives.
• The total motoring load must not exceed the rated load for the drives
sourcing the DC power. Each follower drive must be sized for the motor
load connected to it.
• Total available converter power is derated by 30%.
• The maximum number of drives configured in the project file as
Shared AC/DC is restricted according to
Table 87 on page 216
.
• The maximum number of drives configured in the project file as
Shared DC is restricted according to
Table 86 on page 215
.
• Shared AC/DC hybrid configurations support Bulletin 2198 capacitor
modules.
Figure 102 - Typical Shared AC/DC Hybrid Configuration
(1) For Bulletin 2198 capacitor module maximum values, refer to the Kinetix 5500 Capacitor Module Installation Instructions,
publication
.
For an example shared AC/DC hybrid installation with additional details, refer
to
Typical Shared AC/DC Bus Hybrid Installations
Bonded Cabinet
Ground
Three-phase
Input Power
24V Input
Control Power
2198-H040-ERSx
Common-bus (converter)
Leader Drives
2198-H008-ERSx
Common-bus (inverter)
Follower Drives
2198-CAPMOD-1300 Capacitor Module
(1)
(optional component)
DC Bus Connections