Kinetix 5500 Safe Torque-off - Hardwired Safety

Chapter 9

Safe Torque-off Wiring Requirements

The safe torque-off (STO) connector uses spring tension to secure the wire.
Depress the tab, along side each pin, to release the wire. Two rows of pins are
provided for drive-to-drive connections. Wire must be copper with 75 °C
(167 °F) minimum rating.

Figure 70 - Safe Torque-off (STO) Terminal Plug

Table 76 - Safe Torque-off (STO) Terminal Plug Wiring

IMPORTANT

The National Electrical Code and local electrical codes take precedence over the
values and methods provided.

IMPORTANT

Stranded wires must terminate with ferrules to prevent short circuits, per table
D.7 of EN ISO 13849-2.

1

2

3

4

5

SB+

SB-

S1

SC

S2

Remo

ve

For DC

Bus Only

Kinetix 5500 Drive
Top View

Safe Torque-off (STO) Connector

Recommended Wire
Size
mm

2

(AWG)

Strip Length
mm (in.)

Torque Value
N•m (lb•in)

Pin Signal

STO-1
STO-2
STO-3
STO-4
STO-5

SB+
SB-
S1
SC
S2

1.5…0.2
(16…24)

10 (0.25)

N/A

IMPORTANT

To improve system performance, run wires and cables in the wireways as
established in

Establishing Noise Zones

beginning on

page 39

.