Test Run Graphic Displays

FactoryTalk View ME software provides a Test Display mode to test
the animation and assigned tags connected to objects in a graphic
display. Any information, warning, or errors are logged to the
diagnostic list for your review.

Test Display mode tests all objects in a display:

Button objects

Numeric and string object to verify that correct values are
displayed

Objects that require user input

Objects that use animation

For each object tested, review and correct any errors and warnings
logged to the diagnostic list. Retest the display object before
proceeding to the next object.

Backspace

End

Enter

Home

Move Left

Move Right

Move Down

Page Up

Page Down

No visible error message or error condition
is displayed.

Sort Alarm

Reset Alarm

Alarm Banner

Alarm Status List

No visible error message or error condition
is displayed.

Display Print

No visible error message or error condition
is displayed.

Trend

This object appears not to have any pens
and does not perform real-time trending.

Time and Date

No visible error message or error condition
is displayed.

Object Error Mode

Graphic Object

Visible Error Mode

IMPORTANT

In Test Display mode, objects in the display are activated and
connected to assigned tags. Only tags connected to objects in
the display will work. Links to other displays or alarms,
including data logging, macros, global connections, and
information messages will not work. Configure communication
to the PLC controller before test running the display or all
objects will show their error states.