Chapter 7 Qualify the Runtime Application
Test Run Graphic Displays
FactoryTalk View ME software provides a Test Display mode to test
the animation and assigned tags connected to objects in a graphic
display. Any information, warning, or errors are logged to the
diagnostic list for your review.
Test Display mode tests all objects in a display:
•
Button objects
•
Numeric and string object to verify that correct values are
displayed
•
Objects that require user input
•
Objects that use animation
For each object tested, review and correct any errors and warnings
logged to the diagnostic list. Retest the display object before
proceeding to the next object.
•
Backspace
•
End
•
Enter
•
Home
•
Move Left
•
Move Right
•
Move Down
•
Page Up
•
Page Down
No visible error message or error condition
is displayed.
•
Sort Alarm
•
Reset Alarm
•
Alarm Banner
•
Alarm Status List
No visible error message or error condition
is displayed.
Display Print
No visible error message or error condition
is displayed.
Trend
This object appears not to have any pens
and does not perform real-time trending.
Time and Date
No visible error message or error condition
is displayed.
Object Error Mode
Graphic Object
Visible Error Mode
IMPORTANT
In Test Display mode, objects in the display are activated and
connected to assigned tags. Only tags connected to objects in
the display will work. Links to other displays or alarms,
including data logging, macros, global connections, and
information messages will not work. Configure communication
to the PLC controller before test running the display or all
objects will show their error states.