Review Unsupported Features and Implement Workarounds for Migration Issues Chapter 6

Reviewing Unsupported
Features

Some PanelBuilder 1400e objects or features are not supported in
FactoryTalk View Machine Edition software. Compare the conversion
log with the information on unsupported features to assist with
updates to your migrated application. Additional information is
provided where it is possible to achieve the same result using another
option or work around in your migrated application.

Unsupported Objects or Features in FactoryTalk View Machine Edition

For this PanelBuilder 1400e object

These features are unsupported
in FactoryTalk View ME software

Additional Information

Trend

Blinking Pens

Date Labels on X-Axis

Date is displayed in the trend title.

Background Screen Plotting

You can plot tag values in the background by
assigning the tags to a data log model. Tags
configured for background screen plotting are
automatically assigned to a data log model on
conversion. However, data log models do not plot
expression values. Expressions configured for
background screen plotting are not converted.

Scrolling List Objects

Cursor List

Multistate Indicator Object List

Local Message Object List

Numeric Data Display Object List

Blank States

For information on replacement objects in
FactoryTalk View ME software, refer to page 47.

Set Bit Cursor Point

Object Not Supported

For information on replacement objects , refer to ID:
44265 in the Knowledgebase and also to page 68.

Numeric Display

Polarity

If a PanelBuilder 1400e application was configured
with the polarity control requiring a negative number
to display the minus sign, the numeric display will
not work properly after the application is converted.

Implicit

The implicit option in a PanelBuilder 1400e
application is converted to a fixed position in the
new object. Review these objects to verify that the
number of digits and decimal places are adequate
for displaying the correct value.

Numeric Input Cursor Point

Fixed Position Decimal

Fixed Position Decimal will convert correctly. You
need to remove the comments from the expressions.

PLC Controlled Decimal Display

PLC Controlled Decimal Display may or may not
convert correctly. For information on a workaround in
FactoryTalk View ME software, refer to page 81.

Retain Cursor on Cancel

Goto Configure Mode Button

Object not converted