Review Unsupported Features and Implement Workarounds for Migration Issues Chapter 6

19. On the Connections tab of

your piloted control list
selector, assign the
appropriate tag to the
Visible States connection.

This is the address syntax for the Visible States tag.

{[PLC5]N7:0,L5}

The visible state ladder logic changes are now complete.

When the Main Routine runs, the JSR instruction jumps to the
new program file you created.

In the new program file, the FactoryTalk View ME piloted
control list selector writes the visible states into the elements of
the new data file you created.

The ladder logic in the program file moves the contents of the
elements into the original Visible State x to PLC tags that were
defined in the cursor list object, and then returns to the Main
Routine.

Replace

With

N7:0

The first element in the data file you created.

5 in L5

The number of elements you entered in the new data file or the
number of visible states in the original cursor list object.

PLC5

Shortcut name you defined in Communication Setup of RSLinx
Enterprise software.