Review Unsupported Features and Implement Workarounds for Migration Issues Chapter 6

Data Types

Block Tags

Block tags monitor alarms in PanelBuilder 1400e
applications and are converted to bit arrays. An error
is recorded in the conversion log.

Analog Tags with One Bit Length

PanelBuilder 1400e analog tags that are one bit in
length (0 is min, 1 is max) convert to analog tags in
FactoryTalk View ME software, but the value is
0 and -1 (all bits off, all bits on). This feature is
typically used for indicator objects with two states.
In a FactoryTalk View application, this results in an
incorrect state. Change analog tags to bit data types.

Important: No message appears in the conversion
log. Modify any analog tags that are one bit in
length.

File Transfers

Transfer Inhibit

These three controls are not necessary in FactoryTalk
View ME software because the transfer utility lets
you transfer the runtime project file while running a
project on the runtime terminal.

Transfer Request

Transfer Status

Design Time Features

Tag Cross-Reference

Screen Captures

Application Validation

Application memory usage
calculation

Saving applications to a user
specified location

Tag Search and Replace

Use tag substitution on each page or see
Knowledgebase ID: 29942. RSView Graphic Tags
Search and Replace using Graphics XML Exported
Files

Default Object/Graphic Display
Settings

Power Up Options

Write Last Terminal State to
Controller

Unsupported Objects or Features in FactoryTalk View Machine Edition

For this PanelBuilder 1400e object

These features are unsupported
in FactoryTalk View ME software

Additional Information