Rockwell Automation 2706-ND1 DL40 OFFLINE PROGRAMMING SFTWR.USER MANUAL User Manual
Page 73
Chapter 5
The Develop Menu
5 – 28
•
the DL40 message display leaves the Run Mode
Important: AutoClear will de-energize the alarm relay only if the message
which is cleared has the
Energize relay
enabled.
!
ATTENTION:
Use the relay for annunciator purposes only. Do
not use it for control.
Select
Yes
to activate or
No
to deactivate.
Send message to the stack
When a message is triggered, enabling this attribute will put the message
number on the Historical Events Stack. Variables will also be placed on the
stack. Stacked messages can also be time stamped with the time the message
was triggered and/or run.
Important Even if AutoRepeat is enabled, the message number (and time)
will be put on the Historical Events Stack only once each time
the message is triggered and/or run rather than each time it
repeats.
The message number, variables, and time (if applicable)
will be put on the Historical Events Stack while the message is
running or repeating only when updates to variables are
received by the DL40
For more information on the Historical Events Stack and time stamping, refer
to the Bulletin 2706 Dataliner Message Display DL40 Series User Manual
(Publication 2706-807).
Select
Yes
to activate or
No
to deactivate.
Send message time to the stack
Enabling this attribute allows for time and date stamping of messages sent to
the Historical Events Stack.
Select
Yes
to activate or
No
to deactivate.
Hide message on display
When activated, the message will not appear on the DL40, but rather will be
sent to a slave display, printer, tape recorder, or placed on the Historical
Events Stack. The other attribute settings for the message determine its
destination(s).
For example, assume
Hide message on display
is enabled, as are
message
and
Send message to slave number 2
. There will be no
change on the DL40 display when the message runs, although a copy of the
message will be printed and it will be displayed on the slave addressed as
2
.