Chapter 6
The Transfer Menu
6 – 17
DH+ Network Access
Select
Local
if the PLC to which the DL40 is attached is on the same DH+
link as the programming computer.
Select
Remote (Bridge)
if the PLC to which the DL40 is attached is on a
separate DH+ link from the DH+ link to which your programming computer
is attached, with the two connected by Data Highway.
If you select
Remote (Bridge)
, then you must specify the Local and Remote
Bridge Addresses.
Parameter
Acceptable values
Local Bridge Address
0 to 376 (octal)
Remote Bridge Address
0 to 376 (octal)
The
Local Bridge Address
is the Data Highway address that you assign to
the module connecting the DH+ link on which your programming computer
resides to the Data Highway. This address must match the settings of the DIP
switches on the module.
The
Remote Bridge Address
is the Data Highway address that you assign
to the module connecting the DH+ link on which the PLC-5 to which the
DL40 is connected resides to the Data Highway. This address must match the
settings of the DIP switches on the module.
Setting Device Parameters for an Ethernet Network
Additional transfer parameters may be necessary when you select an Ethernet
communications device. For Ethernet devices, you must specify the
Routing
,
Pushwheel
, and
Channel
.