Chapter 3
Installing the Software
3 – 7
9 If you are using a card other than the 1770-KF2, the contents of the
CFG_KT.INI
file should be similar to the format shown in the sample file
below. This sample is for a 1784-KT board:
[DTL_KT.Options]
①
PATH=C:\ABIC\BIN
②
③
[DTL_KT.1]
④
DEVICE=KT
⑤
MEMORY=C800
⑥
PROTOCOL=DHPLUS
⑦
IRQ=5
⑧
STATION=77
⑨
NAME=DTL_KT 1
⑩
In this file:
① This line identifies the file and prefaces a section of the file used to record
information common to all the communications interface cards on your
system.
②
PATH line that designates the directory where the INTERCHANGE
server programs are located. This will be the same value for all interface
cards on your system.
③
Blank line to separate sections and improve readability.
④
This line identifies the general class of hardware device (in this case a KT
device) and a logical pushwheel identifier of 1. Note: The DL40 Offline
Programming Software assumes that pushwheel 1 is used. Use only
pushwheel 1 when communicating with the DL40 Offline Programming
Software.
⑤
DEVICE line that specifies the exact communication interface card used.
Acceptable values include KT, KTX, KL, KT2, or PCMK.
⑥
MEMORY line that matches the dip switch settings on the interface card.
⑦
PROTOCOL line that identifies the protocol in use.
⑧
IRQ line that matches the dip switch settings on the interface card.
⑨ STATION line designates the octal station address on the local
communications link.
⑩
NAME is a unique string you define to specify to this configuration.