Chapter 5
The Develop Menu
5 – 26
automatically
attribute is active) unless the message contains changed
variable data. If new variable data is received while the message is running,
then the message will be printed more than once. Select
Yes
to activate or
No
to deactivate.
Send message to Slave (address) number
If you enter a slave number here and a message is triggered via the Remote
I/O or Parallel or Keyboard ports, the message will be sent to the slave with
the specified address. This attribute is valid for all Run Modes. However, the
slave address set when operating in the Message/Variable/Slave Run Mode
overrides this attribute.
Important: To send any message to a slave,
Ports
→
RS-485 Port
→
Port
Use
must be set to
DL Slaves
. Refer to page 5 – 35 for
information on the Ports menu.
If the
Repeat message automatically
attribute is active, the message will
be sent to the slave each time it repeats. If the message has embedded
variables, it will be sent to the slave each time new variable values are
received during the message wait time. Possible values for this field include:
Entry:
Which means:
0
Don’t send to slave
1 through 126
Send to the single identified slave address
127
Send to all slaves
Wait time for message
This setting can mean either of two things to the message display.
If you have activated
Scroll message
, the value here represents the
scrolling rate in tenths of a second. For example, a value of 8 here will result
in display of the next new character in a message every 0.8 seconds.
If
Scroll message
is not active, then the value here represents the number
of seconds a message will appear on the message display. For example, a
value of 5 here will assure that the message will appear on screen for 5
seconds whenever it runs.
A value of zero (0) will allow the message to remain displayed until the next
message trigger is received. This will allow the PLC or SLC to control
messaging times.
Acceptable values for this field can range from 0 through 31.
Clear message automatically
Sometimes referred to as AutoClear, activating this menu item instructs the
DL40 to clear the message from the display after the
Wait Time for
message
has expired even if no other messages have been triggered.