Chapter 3
Installing the Software
3 – 9
10 If you are using the 1770-KF2 communications interface card, the
contents of the
CFG_KT.INI
file should be similar to the format shown in
the sample file below:
[DTL_KT.Options]
PATH=C:\ABIC\BIN
[DTL_DF1.1]
DEVICE=DF1
BAUD=9600
IRQ=4
COM_PORT=2
NAME=DTL_DF1
ERROR=1
①
PARITY=0
②
DUPLEX=1
③
①
0=BCC,1=CRC
②
0=No Parity, 1=Even Parity
③ 0=Half Duplex, 1=Full Duplex
11 Save the file. If you are using the DOS text editor, type:
[ALT]FXY
If you are using an Ethernet link and want to enable PLC PassThrough file
transfers, you must first modify your
CONFIG.SYS
and
AUTOEXEC.BAT
files, and install and configure the following products on your PC:
•
Allen-Bradley Ethernet communications interface card (Cat. Nos.
6628-A5 or -A7) or equivalent
•
FTP’s PC/TCP Software for DOS/Windows (FTP Cat. No. PC-210)
Install Ethernet Card
Follow the instructions that came with your Allen-Bradley Ethernet
communications interface card to install and configure it on your personal
computer.
Install the PC/TCP Software
Follow the instructions that came with FTP’s PC/TCP Software to install it
on your personal computer.
Install the Offline Programming Software
Perform the basic installation procedure described earlier in this chapter to
install the Offline Programming Software on your personal computer.
Installing the Software for
Ethernet PLC PassThrough