Hart configuration – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 92

background image

92

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

Chapter 7

Configure the Modules with RSLogix 5000 Software

HART Configuration

The Input Data formats on the General tab let you access HART field device data
through automatic collection of the HART Field Device Process Variables and
Health information.

You can also access HART field device data with pass-through messages. See

Getting HART Data By Using CIP MSG on page 121

and

HART Modules

Used with Asset Management Software on page 141

for more information.

Table 20

shows which configuration options provide HART data in the input tag

and which provide pass-through message access.

Even if you are not enabling HART on all channels, the Analog and HART PV
input tag includes space for the data, but it will be marked with a HARTFault to
indicate it is not valid. This lets you add HART instruments later without
disturbing the tag layout.

Table 20 - HART Data Configuration Options

Input Data Format

Enable HART Checkbox

HART Data Input Tag Present?

Pass-through Message Access for
MSG or Asset Management

Analog only

Not checked

No

No

Checked

Yes

Analog and HART PV

Not checked

Fields present in tag, but data for
this channel not valid

No

Checked

Yes

Yes

Analog and HART by Channel

Not checked

Fields present in tag, but data for
this channel not valid

No

Checked

Yes

Yes