Using msg instructions to access the hart object – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 122

background image

122

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

Chapter 8

Getting HART Data By Using CIP MSG

Using MSG Instructions to
Access the HART Object

Both categories of MSG are handled by the HART Object contained in the
module. There is one HART Object for each channel. Some CIP messages can be
sent to the Class Instance or Instance 0 of the HART object. Most MSGs are sent
to a specific instance of the HART object associated with a particular channel.

This table shows channel and instance correspondence.

These tables show service codes for CIP services.

Channel

Instance

0

1

1

2

2

3

3

4

15

16

Class

Service Code

Function

16#35D

16#4B

Read Dynamic Variables

16#4C

Read Additional Status

16#4D

Get HART Device Information

Class

Service Code

Pass-through Messages

16#35D

16#4E

Init

16#4F

Query

16#50

Flush Queue

TIP

The 16# means this number is Hex display style.