beautypg.com

Configure all channels – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 101

background image

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

101

Configure the Modules with RSLogix 5000 Software Chapter 7

Configure All Channels

Use this table to configure the parameters on the Configuration tab that apply to
all the channels..

Parameter

Action

Notes

Available in
Hard Run mode?

Real Time Sample (RTS)

Choose a value from
0…10,000.

Determines the interval of time at which updated information is supplied to the

controller.

The default is 88.
See

Real Time Sample (RTS) on page 41

for more information.

Refer to the

Real Time Sample Values table on page 101

for RTS choices

available for each Module Filter setting.

No

Module Filter (-3 dB)

Choose a value from
the pull-down menu.

Because the digital HART communication signals are in the 1200…2400 Hz

range, the module filter can not be set to 1000 Hz if HART is enabled.

Refer to the

Module Filter Values table on page 103

to choose a value.

See

Module Filter on page 55

for more information.

No

Keep HART Replies

Choose a value from
1…255 s.

HART replies that are received from the Field Device in response to

pass-through messages you have sent are kept for this long. You must retrieve
them within this time or the module discards them.

The default is 15.

See

Getting HART Data By Using CIP MSG on page 121

for more information.

No

Pass through
(1756-IF8H module only)

Choose a value from
the pull-down menu.

Determines how often pass-through messages occur.

Once per two channels scanned (default)- After 2 channels have PVs scanned

to the input tag, a pass-through message is sent (if one is pending).

Once per module scan - Choose this value if you want to minimize the impact

pass-through message clients have on reading the PVs into the input tag.

Once per channel scan - After each channel has its PVs scanned to the input

tag, a pass-through message is sent (if one is pending). Choose this value if
you want to give pass-through messages from clients, such as FactoryTalk
AssetCentre, higher priority than reading PV, SV, TV, FV and field device
health into the input tag. See the

Pass-through Setting, Ratio, and Priority

table on page 101

for more information.

No

IMPORTANT

We do not recommend a value of less than 15 s.

Table 21 - Real Time Sample Values

Module Filter, Hz

Low Limit

High Limit

10

488

10000

15

328

20

248

50

88

60

88

100 (default)

56

250

28

1000

18

Table 22 - Pass-through Setting, Ratio, and Priority

Setting

Scan:Pass-through ratio

Gives priority to

Once per channel scan

1:1

Asset management

Once per two channels scanned

1:2

Default setting

Once per module scan

1:8

Input tag scan