Tag Definitions Appendix A
ConfigurationChanged
BOOL
Decimal
The field device configuration has changed and new field device configuration information can be
obtained from the 1756-IF16H module via CIP MSG GetDeviceInfo, which will clear this bit.
MaintenanceRequired
BOOL
Bit 0 of Extended Device Status (if using CMD 9, or from CMD 48 if supported).
BrokenWire
BOOL
Decimal
Indicates that current is not flowing through the module as expected. This might be caused by
broken wiring, RTB removal, or a powered-off field device.
HARTFault
BOOL
Decimal
Indicates a problem with HART data from the field device on Channel x.
Examples are HART not enabled, HART device not connected, HART communication failure
due to noise.
The following Field Device Status conditions also cause this to be set: Device Malfunction,
PV Out of Limits, Loop Current Saturated, and Loop Current Fixed.
ResponseCode
SINT
Binary
HART communication status byte or Response code from a recent HART reply. See
and Field Device Status on page 195
for more information.
FieldDeviceStatus
SINT
Binary
HART device status byte from a recent HART reply. Indicates the health of the HART Field device.
See
Field Device Status Bit Mask Definitions on page 196
for more information.
AlarmStatus
SINT
Binary
Indicates various alarms on the analog signal.
DeviceVariableAlert
BOOL
AlarmStatus.4, Bit 1 of Extended Device Status. Device reports a problem with some measurement.
Overrange
BOOL
AlarmStatus.5, Signal value over range (over 20 MA).
Underrange
BOOL
AlarmStatus.6, Signal value under range.
(less than 3.4 mA if configured for 4…20 mA).
CalFault
BOOL
AlarmStatus.7, Bad calibration.
PV
REAL
Float
Primary value. This is the same value as signaled on the analog channel and is the most important
measurement made by this device.
SV
REAL
Float
Secondary value
TV
REAL
Float
Third value
FV
REAL
Float
Fourth value
PVStatus
SINT
Hex
Primary status
16#C0 = Connected
16#00 = Not Connected
SVStatus
SINT
Hex
Secondary status
16#C0 = Connected
16#00 = Not Connected
TVStatus
SINT
Hex
Third status
16#C0 = Connected
16#00 = Not Connected
FVStatus
SINT
Hex
Fourth status
16#C0 = Connected
16#00 = Not Connected
Ch01
AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 01 analog and HART data.
Ch02
AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 02 analog and HART data.
Ch03
AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 03 analog and HART data.
Ch04
AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 04 analog and HART data.
Ch05
AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 05 analog and HART data.
Ch06
AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 06 analog and HART data.
Ch07
AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 07 analog and HART data.
Ch08
AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 08 analog and HART data.
Ch09
AB:1756_IF16H_HARTDataAll_Struct:I:0, Channel 09 analog and HART data.
Table 65 - Analog and HART by Channel (AB:1756-IF16H_AnalogHARTbyChannel:I:0)
Member Name
Type
Style
Description