beautypg.com

Connect the ungrounded end of the cable – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 33

background image

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

33

Module Installation Chapter 2

If you cannot ground at the field device, follow these steps.

1.

Prepare one end of the cable as shown in

step 1 on page 32

.

Ground at an earth ground on the chassis.

Connect the drain wire to a chassis mounting tab. Use any chassis
mounting tab that is designated as a functional signal ground.

2.

Connect the insulated wires to the field device.

Connect the Ungrounded End of the Cable

Follow these steps to connect the ungrounded end of the cable to the clamp.

1.

Cut the foil shield and drain wire back to the cable casing and apply shrink
wrap.

2.

Connect the insulated wires to the RTB.

Chassis Mounting Tab

Drain Wire with Ground Lug

4M or 5M (#10 or
#12) Phillips Screw
and Star Washer (or
SEM screw)

4M or 5M (#10 or
#12) Star Washer

20918

Spring Clamp RTB

Cage Clamp RTB

a. Strip 10 mm (0.4 in.) maximum length

of wire.

b. Insert the screwdriver into the inner

hole of the RTB.

c. Insert the wire into the open terminal

and remove the screwdriver.

a. Strip 8.3 mm (0.33 in.) maximum length

of wire.

b. Insert the wire into the open terminal.
c. Turn the screw clockwise to close the

terminal on the wire.