Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual
Page 171
Rockwell Automation Publication 1756-UM533C-EN-P - February 2011
171
Tag Definitions Appendix A
Changed
BOOL
Decimal
An operation was performed that changed the device’s configuration.
Malfunction
BOOL
Decimal
The device detected a serious error or failure that compromises device operation.
AlarmStatus
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch0Fault for Overrange, Underrange, and
CalFault.
HHAlarm
BOOL
Decimal
AlarmStatus.0, If process alarms are configured to latch by setting Ch0Config.ProcessAlarmLatch
this bit remains set even after the condition returns to normal, until reset via explicit CIP message.
This message can be sent from the RSLogix 5000 Module Properties Alarm dialog box or from the
Logix controller via MSG instruction.
LLAlarm
BOOL
Decimal
AlarmStatus.1, If Ch0Config.ProcessAlarmLatch is set, this alarm remains set until it is unlatched.
HAlarm
BOOL
Decimal
AlarmStatus.2, If Ch0Config.ProcessAlarmLatch is set, this alarm remains set until it is unlatched
LAlarm
BOOL
Decimal
AlarmStatus.3, If Ch0Config.ProcessAlarmLatch is set, this alarm remains set until it is unlatched.
RateAlarm
BOOL
Decimal
AlarmStatus.4, Ch0Data changing faster than Ch0RateAlarmLimit.
Both positive and negative changes can cause this alarm.
If Ch0Config.RateAlarmLatch is set, this alarm remains set until it is unlatched.
Overrange
BOOL
Decimal
AlarmStatus.5, Analog signal is greater than or equal to the maximum detectable signal. Because
the signal cannot be measured, it may be significantly above the maximum value.
Underrange
BOOL
Decimal
AlarmStatus.6, Analog signal is less than or equal to the minimum detectable signal. Because the
signal cannot be measured, it may be significantly below the minimum value.
CalFault
BOOL
Decimal
AlarmStatus.7, Set if an error occurs during calibration for Channel x, causing a bad calibration.
Also sets CalFault.
ExtDeviceStatus
SINT
Binary
Extended device status byte.
Maintenance
Required
BOOL
Decimal
Maintenance is needed.
DeviceVariableAlert
BOOL
Decimal
Device variable alert.
PowerLow
BOOL
Decimal
Low power.
PV
REAL
Float
Primary value. This is the same value as signaled on the analog channel and is the most important
measurement made by this device.
SV
REAL
Float
Secondary value.
TV
REAL
Float
Third value.
FV
REAL
Float
Fourth value.
PVStatus
SINT
Hex
Primary status.
16#C0 = Connected.
16#00 = Not Connected.
SVStatus
SINT
Hex
Secondary status.
16#C0 = Connected.
16#00 = Not Connected.
TVStatus
SINT
Hex
Third status
16#C0 = Connected.
16#00 = Not Connected.
FVStatus
SINT
Hex
Fourth status.
16#C0 = Connected.
16#00 = Not Connected.
Ch01
AB:1756_IF8H_HARTDataAll_Struct:I:0, Channel 01 analog and HART data.
Ch02
AB:1756_IF8H_HARTDataAll_Struct:I:0, Channel 02 analog and HART data.
Ch03
AB:1756_IF8H_HARTDataAll_Struct:I:0, Channel 03 analog and HART data.
Ch04
AB:1756_IF8H_HARTDataAll_Struct:I:0, Channel 04 analog and HART data.
Table 61 - Analog and HART by Channel (AB:1756-IF8H_AnalogHARTbyChannel:I:0)
Member Name
Type
Style
Description