Getting HART Data By Using CIP MSG Chapter 8
Read Additional Status (Service Code = 16#4C)
These tables show the request and reply packet structures for the Read Additional
Status service. Reply Size = 2…224 bytes.
Table 34 - Request Packet
Offset
Field
Data Type
Definition
No request data
Request size = 0 bytes
Table 35 - Reply Packet - Request Failed
Offset
Field
Data Type
Definition
0
Status
USINT
Command status
1
Pad
Pad byte
Reply size = 2 bytes
Request Failed
Table 36 - Reply Packet - Request Succeeded
Offset
Offset
Data Type
Definition
0
Status
USINT
Command status
1
Count
Number of Ext Status bytes available
2
…
26
Ext Status Bytes
Extended Status bytes returned by CMD48
7
Pad
Pad type
Reply Size = Instance 1…8: 2…28 bytes; Instance 0: 224 bytes. If sent to Instance 0, all channels of the module will be included in the response, resulting
in 28 bytes per channel (27 bytes of response to the HART Read Additional Status plus 1 byte of pad to align the data to a 32 bit boundary.)