Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual
Page 127

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011
127
Getting HART Data By Using CIP MSG Chapter 8
56…91
Message
HARTMsg
CMD#12, Bytes 0…23
See
for more information.
92
PVCode
SINT
CMD#50, Bytes 0, 16#ff if not supported
93
SVCode
CMD#50, Bytes 1, 16#ff if not supported
94
TVCode
CMD#50, Bytes 2, 16#ff if not supported
95
FVCode
CMD#50, Bytes 3, 16#ff if not supported
96
PVUnits
CMD#3, Byte 4
97
SVUnits
CMD#3, Byte 9, 0 if not present
98
TVUnits
CMD#3, Byte 14, 0 if not present
99
FVUnits
CMD#3, Byte 19, 0 if not present
100
TransferFunction
CMD#15, Byte 1
101
RangeUnits
CMD#15, Byte 2
102…103
Expanded Device
Type Code
CMD#0, Byte 2 if HART revision is < 7
CMD#0, Bytes 1…2 if HART revision is
≥ 7
104…107
PVLowerRange
REAL
CMD#15, Bytes 3…6
108…111
PVUpperRange
CMD#15, Bytes 7…10
112…115
DampingValue
CMD#15, Bytes 11…14
116
WriteProtectCode
SINT
CMD#15, Byte 15
117
Pad_8 for 32 bit
alignment
118…119
Private Label
Manufacturer 16 bit
CMD#0, Byte 2 if HART revision is < 7
CMD#0, Bytes 19…20 if HART revision is
≥ 7
Reply Size = 120 bytes
(1) See
for related information.
Table 39 - Reply Packet - Request Succeeded
Offset
Field
Data Type
Definition
(1)