Module-defined data types, 1756-if16h module, Configuration – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual
Page 173

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011
173
Tag Definitions Appendix A
Module-defined Data
Types, 1756-IF16H Module
These tables describe module-defined data types for the 1756-IF16H module
and include information for configuration and input tags.
Configuration
This table describes the configuration tags available in the 1756-IF16H module.
Table 62 - Configuration (AB:1756_IF16H:C:0)
Member Name
Type
Style
Description
ModuleFilter
(bits 0…7)
SINT
Decimal
See the
Module Filter Values table on page 103
RealTimeSample
(bits 0…15)
INT
Decimal
Milliseconds between reading signal values. See
Real Time Sample (RTS) on page 41
for more
information.
Ch00Config AB:1756_IF16H_ChConfig_Struct:C:0
Config
SINT
Binary
HARTEn
BOOL
Decimal
Ch00Config.Config.7, Enable HART communication. Must be 1 for valid HART data in input tag and
asset management access to HART field device.
RangeType
SINT
Decimal
0 = 0…20 mA
1 = 4 …20 mA
DigitalFilter
INT
Decimal
Time constant of low pass filter in ms. See
for more information.
LowSignal
REAL
Float
Lower current value for scaling to engineering units. Default is 4 mA. Must be less than HighSignal
and more than or equal to the minimum input range. See
Scaling to Engineering Units on page 98
for
more information.
HighSignal
REAL
Float
Upper current value for scaling to engineering units. Default is 20 mA. Must be more than LowSignal
and less than or equal to the maximum input Range. See
Scaling to Engineering Units on page 98
for
more information.
LowEngineering
REAL
Float
Measured quantity in engineering units that results in a signal level equal to LowSignal. See
to Engineering Units on page 98
for more information.
HighEngineering
REAL
Float
Measured quantity in engineering units that results in a signal level equal to HighSignal. See
to Engineering Units on page 98
for more information.
CalBias
REAL
Float
Sensor Offset in engineering units added to the measured signal before reporting Ch00.Data.
Ch01Config
AB:1756_IF16H_ChConfig_Struct:C:0
Ch02Config
AB:1756_IF16H_ChConfig_Struct:C:0
Ch03Config
AB:1756_IF16H_ChConfig_Struct:C:0
Ch04Config
AB:1756_IF16H_ChConfig_Struct:C:0
Ch05Config
AB:1756_IF16H_ChConfig_Struct:C:0
Ch06Config
AB:1756_IF16H_ChConfig_Struct:C:0
Ch07Config
AB:1756_IF16H_ChConfig_Struct:C:0
Ch08Config
AB:1756_IF16H_ChConfig_Struct:C:0
Ch09Config
AB:1756_IF16H_ChConfig_Struct:C:0
Ch10Config
AB:1756_IF16H_ChConfig_Struct:C:0
Ch11Config
AB:1756_IF16H_ChConfig_Struct:C:0
Ch12Config
AB:1756_IF16H_ChConfig_Struct:C:0
Ch13Config
AB:1756_IF16H_ChConfig_Struct:C:0