Rockwell Automation Publication 1756-UM533C-EN-P - February 2011
91
Configure the Modules with RSLogix 5000 Software Chapter 7
General Tab
Complete the se instructions for a general configuration.
1.
On the General tab, do these steps:
a. Type a name for the module.
b. Type an optional description for the module.
c. Select the slot number for the module.
2.
On the Module Definition box, click Change.
The Module Definition dialog box appears.
3.
Complete these actions:
Parameter
Action
Values
Series
Displays the series letter that matches your
module’s series
N/A
Revision
Choose the revision number that matches the label on the
side of your module, be sure that the minor revision
number also matches
N/A
Electronic Keying
Choose the electronic keying method
See
for more information
• Exact Match
• Compatible Module (default)
• Disable Keying
Connection
Choose the connection type
• Data - has more tabs on the Module Properties dialog box
than Listen-only because of configuration settings for
alarms, calibration
• Listen-only - has no configuration data, does not send output
data (1756-OF8H module)
See
for more information.
Input Data
Choose the input data mode
• Analog Only
• Analog and HART PV
• Analog and HART by Channel (available only for
firmware revision 2.1)
for more information.
Coordinated System Time
Not configurable
Timestamped
Data Format
Not configurable
Float